Mobile Home Installation
MOBILE HOME EXHAUST VENT PIPE INSTALLATION GUIDELINES
Use only listed type “L” pellet vent pipe. Pipe should extend at least 3 feet above the part of the roof
through which it passes. The top of the pipe should be at least 2 feet above the highest required ele-
vation of any part of the mobile home within 10 feet of the pipe.
If exhaust vent exits the mobile home at a location other than the roof, and exits at a point 7 feet or
less above the ground level on which the mobile home is position a guard or method of enclosing
the pipe shall be provided at the point of exit for a height of up to 7 feet. The openings, if any, in this
guard shall not allow a 3/4”rod to pass through. A 1/2”rod could pass through but should not be
able to touch the pipe when inserted through the opening a distance of 4 inches.
Bolt
Non-combustible
Floor Pad
Floor
Chassis
IN ADDITION TO THE STANDARD INSTALLATION INSTRUCTIONS, THE FOLLOWING INSTRUCTIONS MAY BE
REQUIRED BY LOCAL, STATE OR FEDERAL BUILDING CODES:
● Stove must be permanently bolted to the floor.
● Stove must have a permanent outside air source.
● Stove must be permanently electrically grounded to the steel chassis of the home. The location selected
for ground attachment to the stove must be dedicated for this purpose.
● Refer to page 17 for list of commonly used vent components.
● NOTE: THE GROUNDING OF THIS PRODUCT, AT INSTALLATION, MUST COMPLY WITH NFPA-70
STANDARDS, CSA C22.1 IN CANADA,AS WELL AS ANY LOCAL CODES.
WARNING:
DO NOT INSTALL IN A SPACE USED AS A BEDROOM.
CAUTION:THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL
AND CEILING/ROOF MUST BE MAINTAINED.